Using limit state method, design a reinforced concrete circular column (with lateral ties) of height 3·0 m. It is subjected to an unfactored axial load of 1150 kN (dead load + live load). Use M25 grade of concrete and Fe500 grade of steel. Take effective length factor as 1·2. Show the design details in a neat sketch.

15 marks · directive: Design

Answer

The core of a good answer

A 400 mm diameter tied circular column with 6 bars of 18 mm (1527 mm², 1.21%) and 8 mm ties at 280 mm centres carries P_u = 1725 kN (capacity about 1753 kN); it is a short column (l_e/D = 9) and the minimum eccentricity is within the 0.05D limit.

An outline written by upsc.help, not an official UPSC answer; every fact checked by a separate review. How we work

What the question asks

A short axially loaded column design under IS 456:2000. Find the factored load, size the section and steel from P_u = 0.4f_ck A_c + 0.67f_y A_sc, check slenderness and minimum eccentricity, then detail longitudinal bars and lateral ties per clause 26.5.3. The sketch shows the cross-section and elevation.

Answer outline

Introduction

P = 1150 kN, P_u = 1.5 × 1150 = 1725 kN; l = 3.0 m, l_e = 1.2 × 3.0 = 3.6 m; f_ck = 25 MPa, f_y = 500 MPa. Clear cover 40 mm.

Step 1: Trial size

Step 2: Slenderness and minimum eccentricity

Step 3: Longitudinal steel

Step 4: Capacity check

Step 5: Lateral ties

Step 6: Sketch details

Conclusion

Provide a 400 mm diameter column, 6 nos. 18 mm Fe500 bars and 8 mm ties at 280 mm c/c; utilisation 1725/1753 ≈ 0.98.