2026 · Electrical Engineering Optional Paper I · 10 marksMainsQuestion 5b

A 110/220 V, 1·5 kVA, 50 Hz, single-phase transformer absorbs 150 W power when supplied from a 10 V DC source to its LV side with HV side shorted. It absorbs 10 W at 0·4 p.f. lag when the source voltage is changed to 10 V, 50 Hz AC at the LV side and HV side shorted. It takes 50 W power at 0·2 p.f. lag with rated voltage at LV side and HV side open. Now, if the transformer is to be used at 60 Hz frequency at rated voltage and kVA, then find (i) the maximum efficiency at unity power factor load and (ii) the no-load current, input power and power factor at the LV side with rated voltage.

Neglect skin effect and stray losses. Assume linear magnetic circuit, core loss without hysteresis component and same R/X ratio at both LV and HV side.

10 marks · directive: Find

Answer

The core of a good answer

Using the exact equivalent circuit (r₁ = 0·667 Ω, R_eq = 1·6 Ω, X_eq = 3·666 Ω at 50 Hz, R꜀ = 242·7 Ω, X_m = 47·66 Ω), at 60 Hz the pure eddy-current core loss stays about 46·6 W, giving (i) maximum efficiency ≈ 86·4% at unity p.f. (at about 5·39 A, 40% load) and (ii) no-load current ≈ 1·91 A, input ≈ 49·0 W at p.f. ≈ 0·233 lag.

An outline written by upsc.help, not an official UPSC answer; every fact checked by a separate review. How we work

What the question asks

The question asks the candidate to separate winding resistance (DC test), total leakage impedance (AC short-circuit test) and the shunt branch (open-circuit test), and then to rescale reactances and core loss for a change of frequency at the same voltage. Key reasoning: reactances are proportional to f, resistances fixed (no skin effect), and eddy loss alone depends on E² only, not on f.

Answer outline

Introduction

All quantities are referred to the LV side. Rated LV current = 1500/110 = 13·64 A. The DC test gives only the LV winding resistance because a DC source produces no transformer action.

Step 1: LV winding resistance from the DC test

Step 2: Equivalent impedance from the AC short-circuit test (50 Hz)

Step 3: Shunt branch from the open-circuit test (50 Hz)

Step 4: Rescale to 60 Hz at 110 V

Step 5: (ii) No-load quantities at 60 Hz

Step 6: (i) Maximum efficiency at unity p.f.

Conclusion

At 60 Hz the core loss is practically unchanged (no hysteresis part, same voltage), so maximum efficiency is about 86·4% at roughly 40% of rated kVA, while the no-load current falls to about 1·91 A at 0·233 p.f. lag. If the simplified approach (all 50 W treated as core loss, shunt branch at the terminals) is used, the answers are η_max ≈ 86·0% and I₀ ≈ 1·91 A at 0·238 p.f., close to the exact values.

Examples and data to cite