A 6·6 kV, three-phase, star-connected, cylindrical rotor alternator develops rated voltage with field current of 5 A on open circuit. It takes 100 A armature current at 0·2 p.f. lag for 1·0 A field current with its armature symmetrically shorted, all at rated speed. The alternator is delivering maximum power at rated speed to 6·6 kV bus with a field current of 4·5 A.
Find the (i) power generated and delivered by the alternator, (ii) load angle and (iii) power factor and reactive power of the alternator.
Assume linear magnetic circuit.
20 marks · directive: Find
The core of a good answer
Z_s = 7·621 Ω at 78·46° (R_a = 1·524 Ω, X_s = 7·467 Ω) and E = 3429·5 V per phase; maximum power to the bus occurs at δ = θ_z = 78·46°, giving power delivered ≈ 4·00 MW, power generated ≈ 5·66 MW (1·66 MW armature copper loss), current 602 A at p.f. ≈ 0·581 leading, and reactive power ≈ 5·60 MVAr absorbed from the bus.
An outline written by upsc.help, not an official UPSC answer; every fact checked by a separate review. How we work
What the question asks
The question uses the open- and short-circuit data to find the synchronous impedance including resistance, then the power-angle equation with R_a, where maximum output occurs at δ equal to the impedance angle rather than 90°. It also asks for the generated (internal) power, which exceeds delivered power by the armature copper loss.
Answer outline
Introduction
Per phase V = 6600/√3 = 3810·5 V. Linear magnetic circuit: open-circuit emf per ampere of field = 3810·5/5 = 762·10 V/A.
Step 1: Synchronous impedance
- At I_f = 1 A, E = 762·10 V drives 100 A on short circuit: Z_s = 762·10/100 = 7·621 Ω
- Short-circuit p.f. 0·2 lag gives θ_z = cos⁻¹ 0·2 = 78·46°
- R_a = 7·621 × 0·2 = 1·524 Ω; X_s = 7·621 × 0·9798 = 7·467 Ω
Step 2: Excitation emf
- E = 762·10 × 4·5 = 3429·5 V per phase (E < V, under-excited)
Step 3: Power-angle equations
- Delivered: P = 3[(EV/Z_s) cos(θ_z − δ) − (V²/Z_s) cos θ_z]
- Generated: P_g = 3[(E²/Z_s) cos θ_z − (EV/Z_s) cos(θ_z + δ)]
- dP/dδ = 0 gives δ = θ_z for maximum power delivered
Step 4: (ii) Load angle and (i) powers
- δ = θ_z = 78·46°
- P_max = 3(V/Z_s)(E − V cos θ_z) = 3 × 500 × (3429·5 − 762·1) = 4·001 × 10⁶ W ≈ 4·00 MW delivered
- I = (E∠78·46° − V∠0°)/Z_s∠78·46° = 602·1 A ∠+54·46°
- Copper loss = 3 × 602·1² × 1·524 = 1·658 MW
- P_g = 4·001 + 1·658 = 5·659 MW ≈ 5·66 MW generated
Step 5: (iii) Power factor and reactive power
- S = 3VI* = 4·001 − j5·600 MVA; |S| = 6·883 MVA
- p.f. = cos 54·46° = 0·581 leading (current leads terminal voltage)
- Q = −5·600 MVAr, i.e. the alternator absorbs about 5·6 MVAr from the bus
Conclusion
The alternator delivers about 4·00 MW (generating 5·66 MW) at a load angle of 78·46°, operating at 0·581 p.f. leading and absorbing about 5·6 MVAr. A numerical sweep of δ confirms the maximum at 78·46°.
Examples and data to cite
- Neglecting R_a would give maximum power at δ = 90°; the large R/X ratio here (0·204) shifts it to the impedance angle and makes copper loss large.
- Raising the field current until E cos δ approaches V would reduce the reactive power absorbed; at 4·5 A the machine is under-excited (E = 3429·5 V < V = 3810·5 V).
Facts to remember
- Z_s = E_oc/I_sc at the same field current (linear magnetic circuit).
- With armature resistance, maximum power output occurs at δ = θ_z = tan⁻¹(X_s/R_a).
- P_out,max per phase = (V/Z_s)(E − V cos θ_z).
- Under-excitation makes a generator connected to a bus absorb reactive power and run at leading p.f.