Determine the efficiency of a 400 km long transmission line delivering 100 MW load at 240 kV, 0·85 lagging p.f. at the receiving end. The series impedance and shunt admittance per kilometre are 0·175 + j0·375 ohm and 5 × 10⁻⁶ mho respectively.
20 marks · directive: Determine
The core of a good answer
Treating the 400 km line as a long line with distributed parameters (A = cosh γl ≈ 0.8555∠4.46°, B = Z_c sinh γl ≈ 157.4∠66.35° Ω, C ≈ 0.001902∠91.36° S), the sending end needs about 274.8 kV and 112.8 MW, so the efficiency is about 88.7 %.
An outline written by upsc.help, not an official UPSC answer; every fact checked by a separate review. How we work
What the question asks
A 400 km line is a long line, so the rigorous method uses the propagation constant and characteristic impedance to get the ABCD constants, then the sending end voltage and current, and finally η = P_R/P_S. The shunt admittance is capacitive (j5 × 10⁻⁶ S/km).
Answer outline
Introduction
Given z = 0.175 + j0.375 Ω/km, y = j5 × 10⁻⁶ S/km, l = 400 km, P_R = 100 MW at V_R = 240 kV line to line, pf 0.85 lagging. Work per phase.
Step 1: Total parameters
- Z = zl = 70 + j150 Ω
- Y = yl = j0.002 S
Step 2: Characteristic impedance and propagation
- Z_c = √(z/y) = √(Z/Y) ≈ 280.86 − j62.31 Ω = 287.7∠−12.51° Ω
- γl = √(ZY) ≈ 0.1246 + j0.5617
Step 3: ABCD constants
- A = D = cosh γl ≈ 0.8529 + j0.0665 = 0.8555∠4.46°
- B = Z_c sinh γl ≈ 63.14 + j144.17 Ω = 157.39∠66.35° Ω
- C = sinh γl/Z_c ≈ 0.001902∠91.36° S
Step 4: Receiving end quantities
- V_R (phase) = 240 000/√3 = 138 564 V ∠0°
- I_R = 100 × 10⁶/(√3 × 240 000 × 0.85) = 283.0 A
- I_R = 283.0∠−31.79° A
Step 5: Sending end voltage and current
- V_S = AV_R + BI_R ≈ 158 663∠12.56° V per phase, that is about 274.8 kV line to line
- I_S = CV_R + DI_R ≈ 258.5∠36.10° A
Step 6: Sending end power
- Phase angle between V_S and I_S = 12.56° − 36.10° = −23.55°, pf ≈ 0.917 leading
- P_S = 3 V_S I_S cos φ_S ≈ 3 × 158 663 × 258.46 × 0.9167 ≈ 112.78 MW
Step 7: Efficiency
- η = P_R/P_S = 100/112.78 ≈ 0.887
- η ≈ 88.7 %
Conclusion
Efficiency ≈ 88.7 % (line loss ≈ 12.8 MW). Check: a nominal π approximation gives about 89.1 %, close to the rigorous value, and AD − BC = 1 holds for the computed constants.
Examples and data to cite
- Answers by the nominal π method (about 89.1 %) differ slightly from the rigorous long line method; for lines over about 250 km the rigorous method is preferred.
Facts to remember
- Long line: A = D = cosh γl, B = Z_c sinh γl, C = (1/Z_c) sinh γl, with γ = √(zy), Z_c = √(z/y).
- V_S = AV_R + BI_R, I_S = CV_R + DI_R; AD − BC = 1 for a passive reciprocal network.
- Efficiency η = P_R/P_S × 100 %.
- Lines of length 250 km or more are classed as long lines (the length ranges are not rigid).
- Numbers recomputed in Python with complex hyperbolic functions: P_S = 112.779 MW, η = 88.67 %.