Determine the efficiency of a 400 km long transmission line delivering 100 MW load at 240 kV, 0·85 lagging p.f. at the receiving end. The series impedance and shunt admittance per kilometre are 0·175 + j0·375 ohm and 5 × 10⁻⁶ mho respectively.

20 marks · directive: Determine

Answer

The core of a good answer

Treating the 400 km line as a long line with distributed parameters (A = cosh γl ≈ 0.8555∠4.46°, B = Z_c sinh γl ≈ 157.4∠66.35° Ω, C ≈ 0.001902∠91.36° S), the sending end needs about 274.8 kV and 112.8 MW, so the efficiency is about 88.7 %.

An outline written by upsc.help, not an official UPSC answer; every fact checked by a separate review. How we work

What the question asks

A 400 km line is a long line, so the rigorous method uses the propagation constant and characteristic impedance to get the ABCD constants, then the sending end voltage and current, and finally η = P_R/P_S. The shunt admittance is capacitive (j5 × 10⁻⁶ S/km).

Answer outline

Introduction

Given z = 0.175 + j0.375 Ω/km, y = j5 × 10⁻⁶ S/km, l = 400 km, P_R = 100 MW at V_R = 240 kV line to line, pf 0.85 lagging. Work per phase.

Step 1: Total parameters

Step 2: Characteristic impedance and propagation

Step 3: ABCD constants

Step 4: Receiving end quantities

Step 5: Sending end voltage and current

Step 6: Sending end power

Step 7: Efficiency

Conclusion

Efficiency ≈ 88.7 % (line loss ≈ 12.8 MW). Check: a nominal π approximation gives about 89.1 %, close to the rigorous value, and AD − BC = 1 holds for the computed constants.

Examples and data to cite