A 3-phase line is terminated by a star-connected resistive load of 800 ohm per phase. The line conductors are equilaterally spaced 2·0 m apart and have a diameter of 2 cm. The voltage wave travelling along the line is of 33 kV. Determine the power reflected by the load and the power consumed by the line.
20 marks · directive: Determine
The core of a good answer
The surge impedance is Z_c = 60 ln(d/r) = 60 ln 200 ≈ 317.9 Ω and the reflection coefficient is (800 − 317.9)/(800 + 317.9) ≈ 0.431. Taking 33 kV as the line voltage of the wave (19.05 kV per phase), the incident power is about 3.43 MW, of which about 0.637 MW is reflected by the load and about 2.79 MW is absorbed at the termination (three phase totals).
An outline written by upsc.help, not an official UPSC answer; every fact checked by a separate review. How we work
What the question asks
This is a travelling wave problem: find the surge (characteristic) impedance of the overhead line from its geometry, then the reflection and refraction coefficients at the resistive termination, and split the incident power into reflected and absorbed parts. The phrase power consumed is read here as the power absorbed by the termination resistance (the power not reflected).
Answer outline
Introduction
Given d = 2.0 m = 200 cm, r = 1 cm, R = 800 Ω per phase (star), and a 33 kV wave on the three phase line, taken as the line voltage, so the wave on each phase is e = 33/√3 = 19.05 kV. Losses are neglected and the usual approximation L = 2 × 10⁻⁷ ln(d/r) H/m, C = 2πε₀/ln(d/r) F/m is used. The phrase power consumed is read as the power absorbed by the termination (the power not reflected).
Step 1: Surge impedance
- Z_c = √(L/C) = 60 ln(d/r) Ω
- Z_c = 60 ln(200/1) = 60 × 5.298 ≈ 317.9 Ω
Step 2: Reflection and refraction coefficients
- ρ = (R − Z_c)/(R + Z_c) = (800 − 317.9)/(800 + 317.9) ≈ 0.4313
- Refraction (transmission) coefficient = 2R/(R + Z_c) = 1 + ρ ≈ 1.4313
Step 3: Voltages per phase
- Incident wave per phase e = 33 000/√3 ≈ 19 053 V
- Reflected voltage e_r = ρe ≈ 0.4313 × 19 053 ≈ 8217 V
- Voltage across the load e_t = (1 + ρ)e ≈ 27 269 V
Step 4: Incident power
- Per phase P_i = e²/Z_c = (19 053)²/317.9 ≈ 1.142 MW
- Three phase P_i = 3 × 1.142 = 3.426 MW (equivalently (33 000)²/317.9)
Step 5: Reflected power
- Per phase P_r = e_r²/Z_c = (8217)²/317.9 ≈ 0.2124 MW
- Three phase P_r ≈ 0.637 MW, equivalently ρ²P_i = 0.186 × 3.426 MW
Step 6: Power absorbed by the termination
- Per phase P_t = e_t²/R = (27 269)²/800 ≈ 0.9295 MW
- Three phase P_t ≈ 2.789 MW
- Check: P_i − P_r = 3.426 − 0.637 = 2.789 MW
Step 7: If 33 kV is read as the voltage of the wave on each phase
- Each phase then carries 3.426 MW incident, 0.637 MW reflected and 2.789 MW absorbed
- Three phase totals become 10.28 MW, 1.91 MW and 8.37 MW
Conclusion
With 33 kV as the line voltage, reflected power ≈ 0.637 MW and absorbed power ≈ 2.79 MW for the three phases together; the energy balance P_i = P_r + P_t checks. If the inductance is calculated with the conductor GMR (0.7788r), Z_c ≈ 325 Ω and the figures change only slightly.
Examples and data to cite
- A line terminated in its surge impedance (here about 318 Ω) appears to the source like an infinitely long line and produces no reflection, which is the basis of surge impedance loading.
- If the 800 Ω load were replaced by a 317.9 Ω load, ρ = 0 and all of the 3.426 MW incident power would be absorbed.
Facts to remember
- Surge impedance of a lossless line Z_c = √(L/C); for a single circuit overhead line Z_c ≈ 60 ln(d/r) Ω.
- Reflection coefficient ρ = (Z_L − Z_c)/(Z_L + Z_c); refraction coefficient τ = 2Z_L/(Z_L + Z_c).
- Power carried by a travelling wave = e²/Z_c.
- Energy balance: incident power = reflected power + transmitted power.
- Numbers recomputed in Python: Z_c = 317.90 Ω, ρ = 0.43126, three phase P_i = 3.4256 MW, P_r = 0.6371 MW, P_t = 2.7885 MW.