A refrigeration system is to cool bread loaves with an average mass of 400 g from 25 °C to −10 °C at a rate of 400 loaves per hour by refrigerated air at −25 °C. Taking the average specific and latent heats of bread to be 2.90 kJ/kg-°C and 109.15 kJ/kg, respectively, determine (1) the rate of heat removal from the bread in kJ/hr and (2) the required volume flow rate of air in m³/hr, if the temperature rise of air is not to exceed 5 °C. The gas constant of air is 0.287 kPa-m³/kg-K. The specific heat of air at average temperature is 1.0 kJ/kg-°C. Take atmospheric air pressure as 101.3 kPa.
10 marks · directive: Determine
The core of a good answer
Bread mass flow is 160 kg/h, so heat removal = 160(2.90 × 35 + 109.15) = 33,704 kJ/h; air needed = 33,704/(1.0 × 5) = 6740.8 kg/h, which at −25 °C and 101.3 kPa (v = 0.703 m³/kg) is about 4739 m³/h.
An outline written by upsc.help, not an official UPSC answer; every fact checked by a separate review. How we work
What the question asks
An energy balance problem. The bread loses sensible heat over the full 35 °C drop plus the latent heat of freezing of its water, as the data supply average values; the air picks up this heat with a 5 °C rise. Convert air mass to volume with the ideal gas law at the air inlet state.
Answer outline
Introduction
Data: 400 loaves/h × 0.4 kg = 160 kg/h; ΔT_bread = 25 − (−10) = 35 °C; c = 2.90 kJ/kg-°C; h_latent = 109.15 kJ/kg; air enters at −25 °C, ΔT_air = 5 °C, cₚ = 1.0 kJ/kg-°C, R = 0.287 kPa-m³/kg-K, P = 101.3 kPa.
Step 1: Heat removed per kg of bread
- Sensible: 2.90 × 35 = 101.5 kJ/kg
- Latent (freezing): 109.15 kJ/kg
- Total = 210.65 kJ/kg
Step 2: (1) Rate of heat removal
- Q = 160 × 210.65 = 33,704 kJ/h (≈ 9.36 kW)
Step 3: Mass flow of air
- m_air = Q/(cₚΔT_air) = 33,704/(1.0 × 5) = 6740.8 kg/h
Step 4: (2) Volume flow of air
- Specific volume at inlet (−25 °C = 248.15 K): v = RT/P = 0.287 × 248.15/101.3 = 0.7031 m³/kg
- V̇ = 6740.8 × 0.7031 = 4739 m³/h
- If evaluated at the mean air temperature (−22.5 °C), v = 0.7101 m³/kg and V̇ ≈ 4787 m³/h; state the basis chosen
Conclusion
Heat removal ≈ 33,700 kJ/h and air volume flow ≈ 4740 m³/h at the fan inlet state. Recomputed in Python.
Facts to remember
- Sensible heat Q = mcΔT; latent heat Q = mh_latent.
- Steady-flow energy balance: heat lost by product = heat gained by air.
- Ideal gas specific volume v = RT/P.
- 1 kW = 3600 kJ/h.