2026 · Mechanical Engineering Optional Paper II · 10 marksMainsQuestion 2aii

A refrigeration system is to cool bread loaves with an average mass of 400 g from 25 °C to −10 °C at a rate of 400 loaves per hour by refrigerated air at −25 °C. Taking the average specific and latent heats of bread to be 2.90 kJ/kg-°C and 109.15 kJ/kg, respectively, determine (1) the rate of heat removal from the bread in kJ/hr and (2) the required volume flow rate of air in m³/hr, if the temperature rise of air is not to exceed 5 °C. The gas constant of air is 0.287 kPa-m³/kg-K. The specific heat of air at average temperature is 1.0 kJ/kg-°C. Take atmospheric air pressure as 101.3 kPa.

10 marks · directive: Determine

Answer

The core of a good answer

Bread mass flow is 160 kg/h, so heat removal = 160(2.90 × 35 + 109.15) = 33,704 kJ/h; air needed = 33,704/(1.0 × 5) = 6740.8 kg/h, which at −25 °C and 101.3 kPa (v = 0.703 m³/kg) is about 4739 m³/h.

An outline written by upsc.help, not an official UPSC answer; every fact checked by a separate review. How we work

What the question asks

An energy balance problem. The bread loses sensible heat over the full 35 °C drop plus the latent heat of freezing of its water, as the data supply average values; the air picks up this heat with a 5 °C rise. Convert air mass to volume with the ideal gas law at the air inlet state.

Answer outline

Introduction

Data: 400 loaves/h × 0.4 kg = 160 kg/h; ΔT_bread = 25 − (−10) = 35 °C; c = 2.90 kJ/kg-°C; h_latent = 109.15 kJ/kg; air enters at −25 °C, ΔT_air = 5 °C, cₚ = 1.0 kJ/kg-°C, R = 0.287 kPa-m³/kg-K, P = 101.3 kPa.

Step 1: Heat removed per kg of bread

Step 2: (1) Rate of heat removal

Step 3: Mass flow of air

Step 4: (2) Volume flow of air

Conclusion

Heat removal ≈ 33,700 kJ/h and air volume flow ≈ 4740 m³/h at the fan inlet state. Recomputed in Python.