Steam at 40 °C is condensed in a power plant using cooling water available at 12 °C. The flow rate of steam is 0.15 kg/s. The cooling water is circulated through a bank of 6 m long and 1.25 cm internal diameter thin copper tubes at a mean velocity of 3.5 m/s, and leaves at a temperature of 20 °C. The tubes are nearly isothermal at 40 °C. Calculate the average heat transfer coefficient between the water and the tubes, and find the number of tubes needed to achieve the indicated heat transfer rate in the condenser. The properties of water at an average temperature may be taken as :
ρ = 998.8 kg/m³
Cₚ = 4184.5 J/kg-°C
h_fg (water) = 2406 kJ/kg
20 marks · directive: Calculate
The core of a good answer
Condenser duty = 0.15 × 2406 = 360.9 kW; each tube carries 0.429 kg/s of water and picks up 14.36 kW, so with ΔT_lm = 23.78 °C and 0.2356 m² of surface, h = 14,361/(0.2356 × 23.78) ≈ 2564 W/m²-°C, and 360.9/14.36 = 25.1, so 26 tubes are needed.
An outline written by upsc.help, not an official UPSC answer; every fact checked by a separate review. How we work
What the question asks
Internal flow with constant surface temperature. Because outlet temperature is given and no transport properties are supplied, the coefficient comes from the energy balance of one tube combined with the log mean temperature difference. The number of tubes follows from total duty divided by duty per tube.
Answer outline
Introduction
T_s = 40 °C, T_i = 12 °C, T_e = 20 °C, D = 0.0125 m, L = 6 m, V = 3.5 m/s, ṁ_steam = 0.15 kg/s, ρ = 998.8 kg/m³, Cₚ = 4184.5 J/kg-°C, h_fg = 2406 kJ/kg.
Step 1: Heat transfer rate in the condenser
- Q = ṁ_steam h_fg = 0.15 × 2406 = 360.9 kW
Step 2: Water flow and heat per tube
- A_c = πD²/4 = 1.2272 × 10⁻⁴ m²
- ṁ_tube = ρVA_c = 998.8 × 3.5 × 1.2272 × 10⁻⁴ = 0.4290 kg/s
- Q_tube = ṁ_tube Cₚ(T_e − T_i) = 0.4290 × 4184.5 × 8 = 14,361 W
Step 3: Log mean temperature difference
- ΔT_i = 40 − 12 = 28 °C; ΔT_e = 40 − 20 = 20 °C
- ΔT_lm = (28 − 20)/ln(28/20) = 23.78 °C
Step 4: Average heat transfer coefficient
- A_s = πDL = π × 0.0125 × 6 = 0.2356 m²
- h = Q_tube/(A_s ΔT_lm) = 14,361/(0.2356 × 23.78) = 2564 W/m²-°C
Step 5: Number of tubes
- Total water flow = 360,900/(4184.5 × 8) = 10.78 kg/s
- n = 360.9/14.361 = 25.1, so 26 tubes (rounded up)
Conclusion
Average h ≈ 2560 W/m²-°C and about 26 tubes are needed. Only density, specific heat and h_fg are supplied, so the energy balance with LMTD is the intended route. Recomputed in Python.
Facts to remember
- Q = ṁh_fg for condensation.
- ṁ = ρVA_c.
- ΔT_lm = (ΔT_i − ΔT_e)/ln(ΔT_i/ΔT_e).