List the deviations that occur in a compression process in actual vapour compression refrigeration cycle in comparison to simple saturated vapour compression refrigeration cycle. Also, specify the reasons for these deviations.
10 marks · directive: List
The core of a good answer
In the theoretical cycle the vapour enters the compressor dry saturated and is compressed isentropically; in practice the suction vapour is superheated, compression is not isentropic because of internal irreversibility, frictional pressure drops occur in the suction and discharge paths, and lubricating oil circulates with the refrigerant; together these raise compressor work and lower COP.
An outline written by upsc.help, not an official UPSC answer; every fact checked by a separate review. How we work
What the question asks
List each deviation, show it on the p-h or T-s diagram, and give the reason. Restrict the answer to the compression process as the question asks, with brief mention of how they affect COP.
Answer outline
Introduction
Simple saturation cycle: vapour enters compressor dry saturated at evaporator pressure, is compressed isentropically to condenser pressure, with no pressure losses.
Deviations and reasons
- Superheated suction vapour: the vapour gains sensible heat above its saturation point before it reaches the compressor inlet
- Non-isentropic compression: internal irreversibility (friction) during compression, ignored in the ideal cycle
- Pressure drops: frictional pressure drop in the suction and discharge paths, so the compressor works between a lower suction and a higher discharge pressure than the evaporator and condenser pressures
- Lubricating oil: oil carried with the refrigerant from the compressor; separators are not fully efficient
Effects on the cycle
- Higher pressure ratio across the compressor and higher discharge temperature
- More work per kg, hence lower COP
- On the p-h diagram the actual compression line starts to the right of the saturated vapour point and ends at higher enthalpy than the isentropic line
Conclusion
Actual compression differs from the ideal isentropic line through suction superheat, irreversibility in compression and frictional pressure losses, which increase work and reduce COP.
Examples and data to cite
- Typical COP values of vapour compression systems are about 2 to 5.
- Larger systems use an oil separator after the compressor to return oil, but piping must still allow oil to drain back by gravity.
Facts to remember
- Ideal compression: isentropic from saturated vapour at evaporator pressure.
- COP = refrigerating effect/compressor work.