2026 · Mechanical Engineering Optional Paper II · 20 marksMainsQuestion 8a

An air-conditioned space is maintained at 25 °C DBT and 50% RH. The outside conditions are 40 °C DBT and 27 °C WBT. The space has a sensible heat gain of 24.5 kW. Conditioned air is supplied to the space as saturated air at 10 °C. The equipment consists of an air washer. The air entering the air washer comprises 25% of outside air, the remainder being recirculated room air. Calculate the—
(i) volume flow rate of air supplied to space;
(ii) room sensible heat factor;
(iii) cooling load (in TR) of air washer.
Psychrometric chart is given at the end. Also, draw the schematic diagram and show the various processes on a skeleton psychrometric chart.

20 marks · directive: Calculate

Answer

The core of a good answer

Using psychrometric relations at 101.325 kPa (room ω = 0.00988, h = 50.3 kJ/kg; outside ω = 0.01716, h = 84.4 kJ/kg; supply ω = 0.00763, h = 29.3 kJ/kg, v = 0.812 m³/kg), the supply air mass flow is 24.5/15.30 = 1.60 kg/s, i.e. about 1.30 m³/s (78 m³/min); RSHF ≈ 0.73; and the air washer load is 1.60 × (58.9 − 29.3) = 47.3 kW ≈ 13.5 TR.

An outline written by upsc.help, not an official UPSC answer; every fact checked by a separate review. How we work

What the question asks

A psychrometric air-conditioning problem with mixing and a cooling-dehumidifying air washer. Fix all states (room, outside, mixture, supply), get the supply mass flow from the room sensible heat, the RSHF from the supply-to-room line, and the washer load from the enthalpy drop of the mixed air. Show the schematic and the processes on the chart.

Answer outline

Introduction

States (computed with standard psychrometric equations; read from the chart in the examination): room R at 25 °C, 50% RH; outside O at 40 °C DBT, 27 °C WBT; mixture M of 25% O and 75% R by mass; supply S saturated at 10 °C. Schematic: outside air and return air mix, pass through the chilled-water air washer (M to S), supply fan delivers S to the room, room air returns. On the chart: O and R joined, M on the line one quarter of the way from R to O; M to S the washer process; S to R the room process.

Step 1: State properties

Step 2: (i) Supply air quantity

Step 3: (ii) Room sensible heat factor

Step 4: (iii) Air washer cooling load

Conclusion

Supply air ≈ 1.30 m³/s (78 m³/min), RSHF ≈ 0.73 and air washer load ≈ 13.5 TR. Values from the printed chart may differ in the second significant figure. Recomputed in Python with the ASHRAE psychrometric equations.