An air-conditioned space is maintained at 25 °C DBT and 50% RH. The outside conditions are 40 °C DBT and 27 °C WBT. The space has a sensible heat gain of 24.5 kW. Conditioned air is supplied to the space as saturated air at 10 °C. The equipment consists of an air washer. The air entering the air washer comprises 25% of outside air, the remainder being recirculated room air. Calculate the—
(i) volume flow rate of air supplied to space;
(ii) room sensible heat factor;
(iii) cooling load (in TR) of air washer.
Psychrometric chart is given at the end. Also, draw the schematic diagram and show the various processes on a skeleton psychrometric chart.
20 marks · directive: Calculate
The core of a good answer
Using psychrometric relations at 101.325 kPa (room ω = 0.00988, h = 50.3 kJ/kg; outside ω = 0.01716, h = 84.4 kJ/kg; supply ω = 0.00763, h = 29.3 kJ/kg, v = 0.812 m³/kg), the supply air mass flow is 24.5/15.30 = 1.60 kg/s, i.e. about 1.30 m³/s (78 m³/min); RSHF ≈ 0.73; and the air washer load is 1.60 × (58.9 − 29.3) = 47.3 kW ≈ 13.5 TR.
An outline written by upsc.help, not an official UPSC answer; every fact checked by a separate review. How we work
What the question asks
A psychrometric air-conditioning problem with mixing and a cooling-dehumidifying air washer. Fix all states (room, outside, mixture, supply), get the supply mass flow from the room sensible heat, the RSHF from the supply-to-room line, and the washer load from the enthalpy drop of the mixed air. Show the schematic and the processes on the chart.
Answer outline
Introduction
States (computed with standard psychrometric equations; read from the chart in the examination): room R at 25 °C, 50% RH; outside O at 40 °C DBT, 27 °C WBT; mixture M of 25% O and 75% R by mass; supply S saturated at 10 °C. Schematic: outside air and return air mix, pass through the chilled-water air washer (M to S), supply fan delivers S to the room, room air returns. On the chart: O and R joined, M on the line one quarter of the way from R to O; M to S the washer process; S to R the room process.
Step 1: State properties
- Room: ω_R = 0.00988 kg/kg, h_R = 50.3 kJ/kg
- Outside: ω_O = 0.01716 kg/kg, h_O = 84.4 kJ/kg
- Supply (10 °C saturated): ω_S = 0.00763 kg/kg, h_S = 29.3 kJ/kg, v_S = 0.812 m³/kg dry air
- Mixture: ω_M = 0.25 × 0.01716 + 0.75 × 0.00988 = 0.01170 kg/kg; h_M = 0.25 × 84.4 + 0.75 × 50.3 = 58.9 kJ/kg; t_M ≈ 28.8 °C
Step 2: (i) Supply air quantity
- Room sensible heat = ṁ(h at 25 °C and ω_S − h_S) = ṁ × 15.30 kJ/kg (humid specific heat 1.020 kJ/kg-K × 15 K)
- ṁ = 24.5/15.30 = 1.601 kg/s dry air
- V̇ = 1.601 × 0.812 = 1.30 m³/s ≈ 78 m³/min
Step 3: (ii) Room sensible heat factor
- Room latent heat = ṁ(h_R − h at 25 °C, ω_S) = 1.601 × 5.73 = 9.18 kW
- RSHF = 24.5/(24.5 + 9.18) = 0.727 ≈ 0.73 (slope of line S to R on the chart protractor)
Step 4: (iii) Air washer cooling load
- Q = ṁ(h_M − h_S) = 1.601 × (58.9 − 29.3) = 47.3 kW
- In TR: 47.3/3.5169 = 13.5 TR (13.4 TR if the enthalpy of condensate leaving at 10 °C is deducted)
Conclusion
Supply air ≈ 1.30 m³/s (78 m³/min), RSHF ≈ 0.73 and air washer load ≈ 13.5 TR. Values from the printed chart may differ in the second significant figure. Recomputed in Python with the ASHRAE psychrometric equations.
Facts to remember
- Humidity ratio ω = mass of water vapour per unit mass of dry air; ω = 0.622 p_v/(P − p_v) from the ideal gas law.
- Adiabatic mixing: ω and h of the mixture are mass-weighted averages.
- Sensible heat factor = sensible heat/total heat (the protractor scale on the chart).
- 1 TR = 3.516853 kW.